Comsys ADF-P300
The ADF P300 is the ideal active filter for small to large size commercial and industrial loads. It is a powerhouse solution and the best choice for most applications because it is such a general purpose active filter.
The state-of-the-art performance of our active filter technology comes encased in a compact cabinet. Each ADF P300 system is delivered with 90-360 A optimization power and the modular design makes it easy and convenient to add future upgrades. ADF P300 units can be configured using the built-in WUI (Web User Interface). No software needs to be installed on your computer to perform commissioning. All that is needed is a computer with an ethernet port and an ethernet cable.
Design and equipment
| Dimensions | 2203x405x636mm [HxWxD] for up to 150A 2259x605x636mm [HxWxD] for up to 300A 2259x805x636mm [HxWxD] for up to 450A |
| Installation | cabinet |
| Weight | According to datasheet |
| Connection | Below, three (3L-PE) or four (3L-N-PE) wire |
| Display | 7” LCD |
| Line fuse | onsite |
| Current transformer | onsite, transformer ratio …/5A suggested, …/1A possibleInstallation Grid- or Loadside possiblePer phase a current transformer is needed (3 pcs.) |
Technical specifications
| Voltage | 208 - 480V (up to 450A) 480 - 690V (up to 270A) |
| Frequency | 45 - 65Hz (floating) |
| Size | Up to 450A at 480V and 270A at 690V per phase |
| Harmonic correction | 2. to the 49. |
| Power factor correction | Capacitive and inductive (selectable) |
| Load balancing | Between two phases and between phase and neutral |
| Response time | <1ms |
| Operating temperature | 0°C to +40°C without derating, above +40°C automatic derating up to +50°C |

