Ablerex APF-Wall-30A

General

Ablerex Enersine active filters can correct any type of harmonic contamination to protect the system from faults (e.g. burnt-out transformers, damaged capacitors, etc.), while also improving the power factor.

Enersine active wall-mount filters offer the most economical and effective solution, while the scalability of the modular ones protects your investment over time.

Design and equipment
Dimensions 598x348x164mm [HxWxD]
Installation wall
Weight 16kg
Connection Below, three (3L-PE) or four (3L-N-PE) wire
Display 2.7” LCD
Line fuse onsite
Current transformer onsite,
transformer ratio …/5A suggested, …/1A possibleInstallation Grid- or Loadside possiblePer phase a current transformer is needed (3 pcs.)

 

Technical specifications
Voltage 400 V +15%, -20%
480V +10%, -20%
Frequency 50 or 60Hz (± 3Hz)
Size 30A per phase
Harmonic correction 2. to the 51.
Power factor correction Capacitive and inductive (selectable)
Load balancing Between two phases and between phase and neutral
Response time 25µs
Operating temperature -10°C to +25°C without derating,
above +25°C automatic derating to 20A